NBR 6118 checks a circular tank wall's hoop tension against the same γs = 1.15 steel partial factor used everywhere else in the code, but its crack-control provisions for a liquid-retaining structure lean on a tighter characteristic crack-width limit than an ordinary building member would be held to.

Every check above runs automatically inside the Structyze Circular Tank module, free to try online — change any input and every downstream number recalculates instantly, with the governing code clause shown next to each result.

The Example We'll Use

  • Circular tank, internal diameter 6.0 m, liquid depth 4.5 m, wall thickness 300 mm
  • Factored hoop tension at the base, Nd = 485 kN/m
  • Concrete C30 (fck = 30 MPa); reinforcement CA-50 (fyd = 434.8 MPa)
  • Target crack width limit wk = 0.2 mm (liquid-retaining exposure class)

Working Through It

Hoop steel required purely for ultimate strength: As = Nd/fyd = 485,000/434.8 ≈ 1,116 mm²/m — straightforward direct tension, no stress-block mechanics involved since hoop action is pure axial tension around the ring.

Crack-width control under NBR 6118's serviceability provisions pushes the actual provided steel up to roughly 1,420 mm²/m once bar spacing and cover are set to hold wk at 0.2 mm rather than the 0.3–0.4 mm typical limit for a dry building element — a 27% increase over the strength-only requirement.

What Governs, and Why

The ultimate-strength hoop check alone would pass at a comfortable utilisation of 0.786, but NBR 6118's tighter liquid-retaining crack-width limit, not ultimate strength, is what actually governs the final reinforcement — the same serviceability-over-strength pattern this series has already found under Eurocode 2 and IS 3370 for the identical tank type.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze Circular Tank module, free to try online — change any input and every downstream number recalculates instantly, with the governing code clause shown next to each result.

The free trial covers a curated set of flagship modules including this one. For the full catalogue — RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why does a water-retaining structure get a tighter crack-width limit than an ordinary building?

A crack wide enough to be cosmetically acceptable in a dry building can still let water seep through a tank wall or accelerate reinforcement corrosion in a permanently wet element, so NBR 6118 (like most codes in this series) tightens the allowable crack width specifically for liquid-retaining and other aggressive-exposure classifications.

Does NBR 6118 have a water-tank-specific design chapter?

No — NBR 6118 is a general concrete-structures code; the liquid-retaining crack-width limit comes from its exposure-class and serviceability tables rather than a tank-specific clause, so this module applies those general provisions with the tighter exposure class selected explicitly for liquid retention.

Final Thoughts

Once again, the serviceability crack-width check rather than ultimate strength sets the real reinforcement quantity on a liquid-retaining structure — worth checking explicitly on every tank design rather than assuming the strength check alone tells the full story.