A gusset plate's net-section tension check at a truss panel point isn't a formality — this module's own worked example, built from the software's shipped default inputs, fails this check even though every single bolt group at the same joint passes with real margin.

Every check above runs automatically inside the Structyze Truss Gusset Plate Connection module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

The Example We'll Use

  • Bolted connection, 3 members (chord + diagonal) at the joint
  • Gusset 10 mm, Fy = 250 MPa, Fu = 410 MPa
  • Bolt M20, Grade 4.6; edge distance 35 mm, pitch 60 mm
  • Member forces: top chord +150 kN, bottom chord −120 kN, diagonal +80 kN (4 bolts each)

Working Through It

Each member's own bolt group checks comfortably: governing capacity per bolt 45.27 kN, group capacity 181.1 kN — the top chord (150 kN) runs tightest at utilisation 0.828, still a genuine pass.

The governing member for the plate itself is the top chord, the largest tensile force at the joint. Net-section tension uses an effective width of just twice the edge distance (2×35 = 70 mm); after deducting the 21 mm bolt hole, only 490 mm² of net area remains, giving a rupture capacity Tdn ≈ 144.6 kN.

That 144.6 kN capacity is below the 150 kN demand — the gusset plate's own net-section rupture genuinely fails at utilisation 1.037, even though block shear (utilisation 0.221) and every bolt group both pass with real margin.

What Governs, and Why

The gusset plate's net-section tension rupture is the single governing check for the whole joint, and it fails — a real, hand-verified result from the software's own shipped defaults, not a contrived example. The narrow effective width (twice the edge distance) leaves too little net area once the bolt hole is deducted from a 10 mm-thick plate to carry 150 kN in tension at Fe410's fu = 410 MPa.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze Truss Gusset Plate Connection module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

For Truss Gusset Plate Connection and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why does this check use such a narrow effective width?

The simplified single-row bolt-line model takes the effective width as twice the edge distance — a conservative, commonly-taught approximation for how much of the plate participates in resisting tension near a single line of bolts, rather than crediting the plate's full physical width, which a multi-row or wider layout would actually engage.

How would you actually fix this specific joint?

Increasing the gusset thickness (even a modest step to 12 mm would bring utilisation down to roughly 0.86), widening the edge distance, or reducing the bolt diameter to shrink the hole deduction would each restore margin — but any change needs re-checking against every other limit state, since a thicker or wider plate also shifts the block-shear areas.

Final Thoughts

This gusset connection is the clearest illustration in this whole series of why the plate-tension check can never be treated as a formality once the bolt groups pass — it's a real, code-accurate failure hiding behind comfortable-looking bolt numbers.