An underground tank adds a load case most above-ground tanks never see under NBR 6118: empty-tank buoyant uplift from groundwater, checked as a separate stability case alongside the usual full-tank hoop and bending demands — the geotechnical mirror image of the liquid-pressure check this series has run for every other tank type.
Every check above runs automatically inside the Structyze Underground Tank module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.
The Example We'll Use
- Underground rectangular tank, plan 6.0 × 4.0 m, wall height 3.5 m, base slab 400 mm
- Design groundwater table at 1.0 m above the base slab (empty-tank condition)
- Self-weight of tank (empty) Gd = 980 kN; buoyant uplift force Ud = 1,176 kN
- Concrete C30 (fck = 30 MPa); reinforcement CA-50
Working Through It
Uplift stability (empty tank, worst case): factor of safety = Gd/Ud = 980/1,176 ≈ 0.833 — below 1.0, meaning self-weight alone cannot resist buoyancy and the tank would float without additional restraint.
With the base slab extended as a counterweight 'kicker' adding 350 kN of soil surcharge over the slab projection, the resisting weight rises to 1,330 kN, restoring a factor of safety of 1,330/1,176 ≈ 1.131 — a legitimate, if tight, margin against flotation.
What Governs, and Why
The buoyant-uplift check, not wall bending or hoop tension, is this tank's real governing case — a reminder that an underground tank's structural design isn't finished once the full-tank wall checks pass; the empty-tank flotation condition needs its own independent verification with its own margin.
Where Structyze Takes Over
Every check above runs automatically inside the Structyze Underground Tank module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.
For Underground Tank and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.
Quick FAQ
Why is the empty tank the critical condition for uplift, not the full tank?
A full tank's own stored liquid weight adds to the resisting mass holding the structure down, so flotation risk is at its worst precisely when the tank is empty (during construction, maintenance, or a drained-down condition) and groundwater is at its highest. That's the reason this check is run as its own separate, worst-case load combination.
What design options exist if the uplift factor of safety comes up short?
Extending the base slab beyond the walls to use soil surcharge as extra dead weight (as done here), adding a structural kicker or counterweight, or installing permanent relief/drainage to lower the design groundwater level are the three most common fixes — each one changes either the resisting weight side or the uplift demand side of the same ratio.
Final Thoughts
NBR 6118 supplies the material and section provisions, but buoyant uplift itself is fundamentally a geotechnical stability check layered on top — both halves need to pass independently before an underground tank design is actually complete.