Each wall of a rectangular tank is designed as a one-way vertical cantilever under triangular hydrostatic pressure — exactly the statics of a cantilever retaining-wall stem with water in place of soil — but skipping the two-way corner plate action that a fuller analysis would include is a deliberately conservative simplification, not an oversight.

Every check above runs automatically inside the Structyze Rectangular Tank module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

The Example We'll Use

  • Internal 8 × 5 m, liquid height 3.5 m
  • Wall 12 in, base slab 14 in; cover 1.5 in
  • Allowable bearing 2.5 ksf
  • Concrete f′c = 4000 psi, steel fy = 60 ksi
  • Vertical bars #5 at 6 in; horizontal #4 at 7 in

Working Through It

Peak hydrostatic pressure pmax = 62.4(11.5) ≈ 718 psf at the base, with ACI 318's fluid load factor of 1.4 (not the ordinary 1.6 used for most live loads): Mu = 1.4H²pmax/6 ≈ 22.1 kip·ft per foot.

Vertical flexure requires As ≈ 0.50 in² per foot against the #5 at 6 in provided (0.62 in²) — calculated demand really governs here, not minimum steel, at utilisation 0.81. One-way shear clears with real margin (0.50).

The design deliberately treats each wall as an isolated one-way cantilever, with no two-way corner plate action modelled — a real tank corner sees horizontal wall-strip moments and reduced vertical moment near the corner, from genuine two-way action that a full PCA-method plate analysis would capture and this simplified model doesn't.

What Governs, and Why

Vertical flexure governs at utilisation 0.81, the tightest of the five checks — actually calculated demand, not a code minimum, unlike many of the shallower tanks in this series. The one-way model is conservative by design: a two-way plate analysis (per PCA's Rectangular Concrete Tanks) would typically show smaller vertical steel plus some horizontal wall-strip steel concentrated near the corners.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze Rectangular Tank module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

For Rectangular Tank and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why is the tank wall's load factor 1.4, not 1.6?

ACI 318 Cl 5.3.2 assigns fluid pressure its own specific load factor of 1.4, distinct from the 1.6 typically applied to live load — reflecting that a known, well-characterized fluid load carries less uncertainty than a generic live load estimate.

When does the two-way corner effect actually matter?

It matters most near the corners themselves, where the one-way model's neglect of horizontal wall-strip moments is least conservative relative to reality — for a tank with a high aspect ratio or unusually tall walls, a full two-way plate analysis is important to running explicitly rather than relying on the one-way simplification's built-in conservatism.

Final Thoughts

The one-way cantilever simplification for a rectangular tank wall is conservative on the vertical steel but silent on the corner region — worth knowing which gap you're accepting before trusting the numbers at a tank's corner.