A pretensioned prestressed concrete beam designed to CSA A23.3 needs a shear design approach that differs from ordinary reinforced concrete shear design — the prestress force's own compressive effect, and the inclined tendon profile's vertical component near the supports, both actively reduce the shear the stirrups need to carry, in a way that has no equivalent in a non-prestressed beam.

Every check above runs automatically inside the Structyze Prestressed Concrete Beam module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

The Example We'll Use

  • Beam: 350 mm × 750 mm, span 15.0 m, pretensioned straight strands with some draped to a harp point, effective prestress force: 1,720 kN
  • Tendon slope near the support (from the harped profile): 6° from horizontal
  • Factored shear demand at the critical section (d_v from the support face): V_f = 410 kN
  • f'c: 50 MPa

Working Through It

Concrete shear resistance V_c for a prestressed section uses CSA A23.3's general method, which incorporates the longitudinal strain at mid-depth — and crucially, that strain calculation is reduced by the prestress force's own compressive effect, since prestress actively decompresses the section and delays shear crack formation compared to an equivalent non-prestressed beam carrying the same external shear. This gives V_c = 195 kN, meaningfully higher than an equivalent non-prestressed section's typical V_c would be.

The vertical component of the harped tendon's prestress force at the critical section directly reduces the net shear the stirrups need to resist: V_p = effective prestress force × sin(6°) = 1720 × 0.105 = 181 kN.

Net shear to be resisted by stirrups: V_f − V_c − V_p = 410 − 195 − 181 = 34 kN — a dramatically smaller remaining shear than the original 410 kN demand, almost entirely absorbed between the prestress-enhanced concrete contribution and the tendon's own vertical force component.

Minimum stirrup reinforcement (10 mm at 300 mm c/c) comfortably covers the remaining 34 kN demand, giving a utilization of only 0.21 for the stirrup design.

What Governs, and Why

Stirrup shear design ends up very lightly loaded at utilization 0.21, but only because two prestress-specific effects — the enhanced concrete shear contribution from decompression, and the harped tendon's own vertical force component — were both correctly credited; skipping either one (treating this as an ordinary non-prestressed shear design) would have demanded far more stirrup reinforcement than this beam actually needs.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze Prestressed Concrete Beam module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

For Prestressed Concrete Beam and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why does prestress force increase the concrete's own shear capacity?

Prestress compression delays the formation of diagonal shear cracks by counteracting the principal tensile stresses that would otherwise initiate cracking at a lower shear force — a non-prestressed section cracks (and transitions to relying more heavily on stirrups) at a lower shear level than an equivalent prestressed section carrying the same external load.

Does every tendon profile provide a useful vertical force component for shear?

Only draped or harped profiles, where the tendon is intentionally inclined near the supports, provide this effect — a straight tendon profile (common in some pretensioned beams) doesn't contribute a vertical force component at all, meaning shear design for a straight-tendon beam relies entirely on the concrete's prestress-enhanced contribution and stirrups, without this additional credit.

Final Thoughts

Prestressed beam shear design isn't ordinary RCC shear design with a prestress label attached — the prestress force actively reduces the shear demand stirrups need to carry, through two really separate mechanisms. That's why a prestressed beam can need dramatically less shear reinforcement than an equivalent non-prestressed beam carrying the same external load.