A composite steel-concrete beam designed to IS 11384, India's code for composite construction, places real weight on correctly establishing the concrete slab's effective width — a value that closely scales the compressive force the slab can contribute, and one that's easy to overestimate if the beam's actual span and spacing aren't carefully checked against the code's limiting rules.

Every check above runs automatically inside the Structyze Composite Beam module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

The Example We'll Use

  • Beam: ISMB 400 steel section, f_y 250 MPa, composite with 130 mm concrete slab, f_ck 25 MPa
  • Span: 6.0 m, beam spacing (centre-to-centre of adjacent composite beams): 3.0 m
  • Design bending moment: 195 kN·m
  • Shear studs: 20 mm diameter, standard headed studs

Working Through It

Effective width per IS 11384 is taken as the lesser of span/4 (for a simply supported beam) and the actual beam spacing: span/4 = 6000/4 = 1500 mm, versus beam spacing of 3000 mm — the span/4 limit governs here, giving an effective width of 1500 mm, meaningfully less than the full tributary spacing a less careful calculation might have assumed.

Concrete compressive force capacity at this effective width: 0.36 × f_ck × effective width × slab thickness (following IS 11384's compressive stress block approach) = 0.36 × 25 × 1500 × 130 × 10⁻³ = 1,755 kN, compared to the steel section's tensile yield force of 1,590 kN — since the concrete's compressive capacity exceeds the steel's tensile capacity, the plastic neutral axis falls within the slab, confirming full composite flexural behavior.

Moment capacity with the neutral axis in the slab: φM_p = 262 kN·m (steel force acting through the composite lever arm to the neutral axis within the slab depth).

Utilization: 195 / 262 = 0.74.

What Governs, and Why

Flexural capacity governs at utilization 0.74, but the result hinges on correctly applying the span/4 effective width limit rather than the full beam spacing — using the uncapped 3000 mm spacing instead would have overstated the concrete's compressive contribution and the beam's resulting capacity, understating the real utilization and giving a falsely comfortable margin.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze Composite Beam module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

For Composite Beam and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why does effective width use the lesser of span-based and spacing-based limits?

The span-based limit reflects that stress in the slab doesn't spread uniformly across its full width instantaneously — shear lag effects mean only a portion of a wide slab actually participates effectively in resisting bending near mid-span, and that effective portion is related to span length, not just how far away the next beam happens to be.

Does a shorter span always mean a smaller effective width?

Yes, proportionally, since the span/4 (or similar span-based fraction) term scales directly with span — a shorter-span composite beam is more likely to have its effective width governed by the span-based limit rather than the beam spacing, compared to a longer-span beam where spacing more often governs instead.

Final Thoughts

Composite beam capacity is only as reliable as the effective width it's built on — and because that width is capped by span, not simply handed over as the full distance to the next beam, skipping the comparison between the two limits is exactly how a composite beam design ends up overstating its own real flexural capacity.