A combined footing carrying two columns behaves like a self-equilibrating beam with no external support — shear and moment must return to specifically zero at both free ends, and because footings carry no stirrups, the steel percentage you provide actually changes how much shear the concrete alone can resist.
Every check above runs automatically inside the Structyze Combined Footing module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.
The Example We'll Use
- Overhang 1.5 m, column spacing 4.0 m, overhang 1.0 m
- Footing 6.5 × 2.2 m, thickness 850 mm, cover 50 mm
- Columns 400 × 400 mm each
- Column 1: dead 700 kN, live 350 kN — Column 2: dead 500 kN, live 250 kN
- Allowable bearing 180 kN/m², concrete M20, steel Fe415
Working Through It
The load resultant sits at x̄ = 3.17 m from the free end, giving an eccentricity of just 0.083 m against a middle-third limit of 1.08 m — comfortably inside, so the plan size is sound. The factored pressure diagram varies from 203.3 kN/m² near column 1 to 174.3 kN/m² at the far end.
Integrating that trapezoidal pressure against the two factored column reactions gives a sagging moment of about 226 kN·m/m in the overhang near column 1, and a hogging moment of about 221 kN·m/m between the columns — both well below the flexural minimum steel requirement on their own.
The real story is one-way shear at d past column 1's face: with only the flexurally-required steel, the concrete shear strength τc (which climbs with the steel percentage pt provided) comes out too low and the check fails. Doubling the longitudinal bars to 2010 mm²/m lifts pt from 0.13% to 0.25%, which raises τc enough to pass — the steel here is sized by shear, not by bending.
What Governs, and Why
One-way shear governs at utilisation 0.91, and it governs the steel quantity itself, not just the concrete thickness — a footing with IS 456's τc-depends-on-pt relationship can genuinely need more bar area purely to pass shear, even once bending is already satisfied. Punching shear at both columns carries wide margin (0.31 and 0.21).
Where Structyze Takes Over
Every check above runs automatically inside the Structyze Combined Footing module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.
For Combined Footing and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.
Quick FAQ
Why would a footing need more steel than bending calls for?
Because IS 456's permissible concrete shear stress τc is itself a function of the tension steel percentage provided — adding bars raises τc and helps the shear check pass, the way adding depth would, and it's often the less disruptive fix.
When is a combined footing needed instead of two isolated footings?
Typically when a property line stops an exterior column's own pad from extending far enough, or when two isolated footings would physically overlap — combining them into one footing lets the resultant land near the centroid instead.
Final Thoughts
A combined footing is one of the clearer examples of why a footing's steel percentage isn't just a bending output — it's an input to its own shear check too, which makes hand iteration actually tedious.