A dedicated fire-water reservoir is structurally just a large circular tank — but scale changes which check actually matters: at a big enough diameter and depth, hoop tension itself, not the code minimum, becomes the number worth watching.

Every check above runs automatically inside the Structyze Fire Water Tank module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

The Example We'll Use

  • Internal diameter 12 m, liquid height 6 m
  • Wall 300 mm, base slab 350 mm, cover 40 mm
  • Allowable bearing 130 kN/m²
  • Concrete C30/37, steel B500
  • Hoop bars φ16 at 175 mm each face; vertical φ12 at 250 mm

Working Through It

At radius r = 6 m, the service hoop tension T = 9.81(6)(6) ≈ 353 kN/m at the base — already large in absolute terms purely from the bigger diameter and deeper water than a typical domestic tank. Factored TEd = 1.2(353) ≈ 424 kN/m.

The required hoop steel, As = 424×10³/435 ≈ 975 mm²/m, is met generously by φ16 at 175 mm each face (2298 mm²/m total) — sized this way specifically for the BS EN 1992-3 crack-width limit under the characteristic (service) combination, not just the ULS check shown.

Base bearing, with the wall, base slab and the full liquid weight summed over the tank's plan area, comes to about 72.4 kN/m² against 130 kN/m² allowable — comfortable margin.

What Governs, and Why

Hoop tension (ULS utilisation 0.42) is a genuinely meaningful number here, not just a formality — the tank is large enough that the code minimum is no longer what's sizing the wall. For a fire reserve that's rarely turned over (and so sees sustained high water level for long periods), the BS EN 1992-3 crack-width limit under the characteristic combination is what actually calls for the generous split-face bar arrangement shown, beyond what the ULS check alone would require.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze Fire Water Tank module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

For Fire Water Tank and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why does hoop tension only become meaningful at this scale?

Hoop tension scales directly with both radius and liquid height (T = γHr) — a small domestic tank's hoop demand is often so far below the crack-control-driven minimum steel that the ULS check barely registers; a 12 m tank with 6 m of water pushes the calculated demand high enough that it actually competes with (though here still stays under) the crack-control requirement.

Is crack width automated in this check?

No — the BS EN 1992-3 crack-width calculation itself isn't automated in this module; the generous split-face bar arrangement shown is sized based on established practice for this class of structure, but a final design should verify crack width explicitly under the characteristic load combination.

Final Thoughts

A fire-water tank is a useful lesson in scale: the same circular-tank mechanics that are almost trivial for a small domestic tank become a genuinely live design constraint once the diameter and depth both grow.