A purlin cleat connection has to handle a truly signed reaction — wind uplift on a roof purlin puts the connection into net upward force instead of the usual downward gravity reaction. And the same three checks apply regardless of which way the force actually points.
Every check above runs automatically inside the Structyze Purlin/Girt Cleat Connection module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.
The Example We'll Use
- Factored reaction +15 kN (gravity, not uplift)
- Cleat thickness 8 mm, depth 120 mm
- Cleat material Fy = 345 MPa, Fu = 450 MPa
- Bolt M12, A325-N, Fnv = 372 MPa
- 2 bolts to purlin, 2 bolts to supporting member
Working Through It
Per-bolt capacity: shear governs at 0.75(372)(113.1)/1000 ≈ 31.55 kN, against a bearing capacity of 77.76 kN — shear is the weaker of the two limit states here.
Both bolt groups — cleat-to-purlin and cleat-to-support — are checked independently against the same 15 kN reaction: 2(31.55) = 63.1 kN capacity each, utilisation 0.238 on both sides.
The cleat plate itself, treated mechanically like a short beam web in shear, carries wide margin: φvVn = 1.0(0.6)(345)(960)/1000 ≈ 198.7 kN against the 15 kN demand.
What Governs, and Why
Both bolt groups govern equally at utilisation 0.238 (identical bolt count and size on each side), well ahead of the cleat plate's own shear capacity at 0.076 — a light, minimum-practical connection typical of roof secondary framing. For an uplift case, the identical three checks apply to the reaction's magnitude regardless of its sign.
Where Structyze Takes Over
Every check above runs automatically inside the Structyze Purlin/Girt Cleat Connection module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.
For Purlin/Girt Cleat Connection and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.
Quick FAQ
Why does the connection not care which direction the force points?
The bolt shear, bearing, and cleat shear-yielding formulas all depend only on the magnitude of the force being transferred, not its direction — a purlin cleat resisting 15 kN of uplift fails (or passes) the identical three checks as one resisting 15 kN of gravity load, just with the physical load path reversed.
What isn't checked in this simplified method?
Block shear rupture of the cleat plate around each bolt group (AISC Ch J4.3) isn't checked here — for a cleat with a small edge distance relative to the bolt diameter, that's worth verifying separately, since a tightly-edge-distanced cleat can fail in block shear before either the bolts or plain plate shear governs.
Final Thoughts
The signed-reaction convention in a purlin cleat check is a small but really important detail — a roof connection sized only for gravity load without checking the uplift case is a common and consequential oversight in light secondary framing.