A cantilever retaining wall under Eurocode 2 needs two separate verification regimes run side by side — EN 1997 geotechnical checks (overturning, sliding, bearing) using Design Approach 1's two load combinations, and EN 1992 structural checks on the stem, toe and heel.

Every check above runs automatically inside the Structyze Cantilever Wall module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

The Example We'll Use

  • Stem height 3.0 m, stem/footing thickness 300/400 mm
  • Toe length 1.0 m, heel length 1.6 m
  • Backfill γ = 18 kN/m³, φ′ = 30° (Ka = 0.333), no surcharge
  • Allowable bearing 150 kN/m², friction coefficient 0.5
  • Concrete C25/30, steel B500

Working Through It

Design Approach 1 requires checking two combinations and taking the worse: Combination 1 factors the actions (γG = 1.35), Combination 2 instead factors the soil strength (γφ′ = 1.25) with unfactored actions. Overturning is verified as an EQU check with γG,dst = 1.1 against γG,stb = 0.9, giving an over-design factor Γ = 5.2 here — comfortable.

Sliding is the tighter check: under Combination 2's reduced soil friction angle (φ′d = 24.8° instead of 30°), the design resistance Rd = 63.7 kN/m against a design thrust of 42.5 kN/m gives Γ = 1.50 — right at the edge of comfortable.

On the structural side, the stem's design moment MEd = 36.4 kN·m/m works through Eurocode 2's K/K′ method to Ast ≈ 350 mm²/m, but the Cl 9.6.3 minimum horizontal steel requirement (300 mm²/m against 314 mm²/m provided) runs almost exactly at its limit.

What Governs, and Why

Sliding under Design Approach 1 Combination 2 is the governing check at Γ = 1.50 — it's specifically the soil-strength-factoring combination that makes sliding critical, since Combination 1 gives a much larger margin on the same geometry. Every structural member ends up governed by minimum steel, not calculated demand.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze Cantilever Wall module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

For Cantilever Wall and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why check two separate load combinations for the same wall?

EN 1997's Design Approach 1 requires verifying both a load-factored case and a soil-strength-factored case because it isn't obvious in advance which one governs a given failure mode — here overturning is dominated by Combination 1's logic while sliding is tighter under Combination 2.

What if the sliding check fails?

A shear key cast into the underside of the base, or a longer heel (which adds more resisting weight), are the standard fixes — both increase sliding resistance without needing a wider overall footprint.

Final Thoughts

Running both Design Approach 1 combinations by hand for every trial geometry is a classic case of repetitive iteration that eats an afternoon on a real retaining-wall design.