A round concrete-filled steel tube (CFST) column, designed to AISC 360 Chapter I, follows a buckling check structurally similar in format to a bare steel column's, but the composite section's effective stiffness and nominal strength calculations both draw closely on the concrete infill's contribution — and AISC 360 requires checking that the steel tube itself provides adequate confinement for that credit to actually apply.

Every check above runs automatically inside the Structyze Composite Column module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

The Example We'll Use

  • Column: 355.6 mm diameter × 9.5 mm wall thickness round HSS, filled with concrete, height 4.2 m, pinned-pinned
  • Steel: F_y = 345 MPa, concrete infill: f'c = 35 MPa
  • Design axial load (LRFD): P_u = 3,650 kN

Working Through It

Confinement check: AISC 360 requires the steel tube's wall thickness-to-diameter ratio to satisfy a minimum limit for the tube to be considered capable of providing adequate confinement to the concrete core — this tube's ratio of 9.5/355.6 = 0.027 comfortably exceeds the code's minimum requirement, confirming the composite section qualifies for full composite action credit.

Nominal compressive strength at zero slenderness (P_no) combines the steel tube's yield strength contribution with the concrete core's strength contribution (using a factor reflecting the confinement benefit for round HSS sections specifically, which AISC 360 credits more generously than for rectangular sections): P_no = 5,920 kN.

Elastic buckling load P_e is calculated using the composite section's effective stiffness (EI)_eff, which combines the steel tube's full stiffness with a reduced contribution from the concrete reflecting long-term and cracking effects, giving P_e = 7,650 kN for this column's length and section.

With P_no/P_e = 5920/7650 = 0.77, AISC 360's inelastic buckling formula applies: P_n = P_no × 0.658^(P_no/P_e) = 5920 × 0.658^0.77 = 4,580 kN. Design capacity: φP_n = 0.75 × 4580 = 3,435 kN.

Utilization: P_u / φP_n = 3650 / 3435 = 1.06 — this column, as sized, narrowly fails its axial capacity check.

What Governs, and Why

The column narrowly fails at utilization 1.06, despite qualifying for full composite confinement credit and a comfortably high P_no/P_e ratio — a useful reminder that confinement eligibility and a favorable stiffness ratio improve a composite column's margin, but don't guarantee adequacy on their own; the actual demand-to-capacity numbers still have to be run through to the end before concluding a design is adequate.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze Composite Column module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

For Composite Column and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why does AISC 360 credit round HSS sections more generously for concrete confinement than rectangular ones?

A round tube applies more uniform, effective confining pressure around its full concrete core perimeter than a rectangular tube does (which tends to concentrate confinement near the corners and provide less restraint along flat faces), so AISC 360's confinement-related strength provisions reflect that genuine mechanical difference between the two shapes.

What's the most direct way to resolve this column's narrow failure?

Increasing the tube diameter or wall thickness squarely increases both the steel and concrete contributions to P_no and improves the stiffness ratio feeding into the inelastic buckling formula, making it generally more effective than simply upgrading concrete strength alone for a column this close to its slenderness-sensitive buckling threshold.

Final Thoughts

A concrete-filled tube column's confinement eligibility is a precondition for the favorable composite strength calculation, not a substitute for actually running that calculation through to a final utilization number — so this column's narrow failure, despite ticking the confinement and stiffness-ratio boxes, still needed the full capacity check carried out before being called adequate.