Every check above runs automatically inside the Structyze Purlin/Girt Cleat Connection module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

The Example We'll Use

  • Factored reaction 15 kN (gravity, positive)
  • Cleat thickness 8 mm, depth 120 mm, fy = 300 MPa
  • Bolts M12, Grade 8.8, fuf = 830 MPa; 2 to purlin, 2 to support

Working Through It

Bolt capacity: gross area 113.1 mm², Ac = 0.75(113.1) ≈ 84.8 mm²; φVf = 0.8(0.62)(830)(84.8)/1000 ≈ 34.9 kN; φVb = 0.8(3.2)(12)(8)(300)/1000 ≈ 73.7 kN — shear governs at 34.9 kN per bolt.

Both bolt groups — to purlin and to support. Come out identical since both use the same bolt size and count: 34.9(2) = 69.8 kN capacity each, utilisation 0.215.

Cleat plate shear: φVu = 0.9(0.6)(960)(300)/1000 ≈ 155.5 kN against the 15 kN demand — utilisation just 0.096, the loosest check of all three.

What Governs, and Why

Every check runs loose (utilisation ≤ 0.22) — a light purlin reaction against a compact 2-bolt-each-side cleat leaves considerable spare capacity in both the bolt groups and the cleat's own shear yielding, typical of a purlin/girt connection sized more by practical minimum bolt count and plate size than by the reaction itself.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze Purlin/Girt Cleat Connection module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

For Purlin/Girt Cleat Connection and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why would a connection be sized by practical minimums rather than the calculated demand?

Below a certain reaction magnitude, a bolted cleat connection can't realistically get any smaller — two bolts is typically the practical minimum for a connection carrying any real load (for redundancy and to resist minor eccentricity), and an 8 mm cleat plate is often the thinnest practical stock size for a structural connection. Once those practical minimums are in place, the calculated utilisation simply reflects how far below capacity the connection happens to sit, not a deliberate design target.

What's the bearing calculation quirk noted for this module?

Bolt bearing capacity here uses the cleat's own yield stress Fy in place of a separate ultimate stress Fu, which this module doesn't collect as a separate input — since Fy < Fu always, this understates rather than overstates the bearing capacity, and doesn't affect this example's outcome since bolt shear already governs regardless.

Final Thoughts

A connection where every check lands comfortably under 0.25 utilisation is a useful reminder that not every structural member or connection is sized by its calculated demand — practical minimums often do the real work for light secondary framing.