A three-column mat strip's moment diagram is truly richer than a simple hog-and-sag beam — directly under an unusually heavy interior column, a secondary local sagging peak can develop, sandwiched between two hogging troughs, and checking only the single largest positive moment in the diagram would miss it entirely.

Every check above runs automatically inside the Structyze Mat Foundation module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

The Example We'll Use

  • Overhang 1 m, spacing 5 m, spacing 5 m, overhang 1 m
  • Strip width 3 m, thickness 700 mm
  • Columns 400 × 400 mm; cover 50 mm
  • Column loads (symmetric): A & C 600/300 kN, B 900/450 kN
  • Allowable bearing 150 kN/m²; concrete M20, steel Fe415

Working Through It

With symmetric loads, the resultant sits exactly on the strip centroid, giving uniform pressure: q = 3150/(12×3) ≈ 87.5 kN/m² against 150 kN/m² allowable.

Integrating the diagram from the free overhang end finds the expected hogging troughs between columns A–B and B–C, peaking at M− ≈ −964.4 kN·m total each. But directly under the heavier column B, the diagram pushes back up to a genuine local sagging peak, M+ ≈ 337.5 kN·m total — distinct from, and larger than, the ordinary overhang sagging peak near column A (≈ 197 kN·m).

One-way shear, just before column B, runs tightest at utilisation 0.96 — and as with the combined footing elsewhere in this series, it's the steel percentage (lifted by the closely-spaced 90 mm top bars, which also handle the hogging moment) that actually clears this check, not the section depth alone.

What Governs, and Why

One-way shear governs at utilisation 0.96, with the secondary sagging peak closely under column B running a separate, distinct case at utilisation 0.50 — a design case that would be missed entirely by checking only the single largest positive moment in the diagram. This is why the strip method integrates the full diagram rather than sampling a handful of representative points.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze Mat Foundation module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

For Mat Foundation and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why would a heavy interior column create a local sagging peak instead of just a deeper hogging trough?

The upward soil pressure under the strip is roughly uniform, but the heavy column's large downward point load locally overwhelms that distributed upward pressure right at its own location, briefly pushing the moment diagram back toward sagging before the surrounding hogging troughs take over again a short distance away — a direct consequence of point loads superimposed on distributed pressure, not a modelling artifact.

When would this secondary peak actually matter for reinforcement?

Whenever an interior column's load is meaningfully heavier than its neighbours — a uniform load pattern across all columns wouldn't produce this effect at all, since there'd be no single point load heavy enough to locally overwhelm the distributed pressure and reverse the local curvature.

Final Thoughts

The secondary sagging peak under a heavy interior column is the clearest illustration in this whole series of why a strip foundation's moment diagram genuinely needs integrating in full, not just checked at the obvious locations a simpler beam analogy would suggest.