A Eurocode 2 waist-slab staircase runs its deflection check right at the edge of its own limit — not failing, but close enough that a slightly longer going or a slightly thinner waist would tip it over, a useful illustration of how tightly this particular check can run even when every other number has room to spare.
Every check above runs automatically inside the Structyze RCC Staircase module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.
The Example We'll Use
- Going length 2.4 m, simply supported
- Waist 150 mm, cover 20 mm
- Riser 150 mm, tread 275 mm
- Superimposed dead 1.0 kN/m², live 4.0 kN/m² (Cat A stair)
- Concrete C25/30, steel B500
Working Through It
The slope factor k = √(275²+150²)/275 ≈ 1.139 inflates the waist self-weight to 4.27 kN/m²; adding the triangular steps' own 1.88 kN/m² gives a combined design load w = 1.35(4.27+1.88+1.0)+1.5(4.0) ≈ 15.65 kN/m.
Being a single simply-supported flight, MEd = wℓ²/8 ≈ 11.3 kN·m/m is exact statics, no approximation. Working through K/K′ gives Ast ≈ 220 mm²/m, well above the 165 mm²/m minimum — calculated demand governs, comfortably covered by φ12 bars at 150 mm (753 mm²/m, utilisation just 0.29).
Deflection, using Eurocode 2's ℓ/d ≤ 20 limit for this member type: ℓ/d = 2400/124 = 19.4 — utilisation 0.97, the tightest check by a wide margin over everything else in the design.
What Governs, and Why
Deflection runs at utilisation 0.97 — by far the tightest check, with bending (0.29), minimum steel (0.22) and shear (0.25) all carrying wide margin. This is a actually close pass, not a comfortable one: a slightly longer going, a marginally thinner waist, or a lower concrete grade could tip this specific check over 1.0 even though every strength check has room to spare.
Where Structyze Takes Over
Every check above runs automatically inside the Structyze RCC Staircase module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.
For RCC Staircase and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.
Quick FAQ
Why would deflection run so much tighter than every strength check on the same flight?
A staircase waist is thin relative to its span (150 mm on a 2.4 m going), and strength checks scale differently with thickness than deflection does — deflection depends on stiffness (proportional to thickness cubed through the second moment of area), so a section that's comfortably strong can still be only just stiff enough, specifically the pattern this series finds repeatedly across thin, lightly-loaded slab-type members.
What's the fix if a real project's staircase geometry pushes this over 1.0?
A thicker waist is the direct fix, since it improves the ℓ/d ratio proportionally; alternatively, if the flight can be supported at an intermediate point (breaking the single simply-supported span into two shorter ones), the effective span driving the deflection check shrinks considerably.
Final Thoughts
A staircase's deflection check running this close to its limit, while every strength number has generous margin, is a genuinely useful warning that 'the numbers passed' doesn't always mean there's room to spare on every check.