AS 4100's gantry girder module checks only each axis's section moment capacity independently — a disclosed simplification that skips lateral-torsional buckling entirely, unlike the ordinary steel beam module elsewhere in this series, which folds a full member capacity including LTB into its bending check.

Every check above runs automatically inside the Structyze Gantry Girder module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

The Example We'll Use

  • Span 6 m
  • Section 450 × 200 × 20 × 12 mm
  • Maximum static wheel load 100 kN
  • Vertical impact factor 25%, lateral surge 10%
  • Material AS/NZS 3679.1 Grade 300, fy = 300 MPa

Working Through It

Section properties: Zp (major) ≈ 2,224,300 mm³, Zpy (minor) ≈ 414,760 mm³. Factored loads: W* = 1.5(100)(1.25) = 187.5 kN, S* = 1.5(100)(0.10) = 15.0 kN.

Design moments: M*x = 187.5(6)/4 = 281.25 kN·m, M*y = 15.0(6)/4 = 22.5 kN·m. Section moment capacities (no LTB reduction applied to either): φMsx ≈ 600.6 kN·m, φMsy ≈ 112.0 kN·m.

What Governs, and Why

The biaxial interaction governs at utilisation 0.669 (281.25/600.6 + 22.5/112.0 = 0.468 + 0.201) — the major-axis term contributes more than double the minor-axis term. A lighter Grade 300 default here gives noticeably more margin than a lower-yield material would, since a higher fy scales up both φMsx and φMsy together.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze Gantry Girder module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

For Gantry Girder and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why does this module skip lateral-torsional buckling when the ordinary beam module includes it?

This is a disclosed, deliberate simplification specific to the gantry girder module — a real gantry girder's compression flange, restrained only at the supports and carrying combined vertical-plus-lateral loading, can be governed by LTB, but that full analysis isn't modelled here. Checking only section capacity in each axis independently is conservative in the sense of being simpler, but not necessarily conservative in the sense of being safe if LTB would actually govern.

What's the practical risk of skipping LTB on a real gantry girder?

If the compression flange's actual unbraced length is long enough that LTB would meaningfully reduce capacity below the plain section capacity checked here, this module's result would overstate the girder's true capacity — a real design should verify LTB separately, especially for a longer-span girder or one without a capping channel providing extra lateral restraint.

Final Thoughts

The gantry girder module's disclosed gap — no LTB check at all. Is a classic case of scope limitation useful to reading before trusting a governing utilisation number at face value.