CSA S16 checks lateral-torsional buckling differently from AISC 360's two-branch Lp/Lr comparison — it compares two moments directly, the elastic critical moment against 0.67 times the plastic moment, through one continuous formula rather than three separate zones.

Every check above runs automatically inside the Structyze Steel Beam module, free to try online — change any input and every downstream number recalculates instantly, with the governing code clause shown next to each result.

The Example We'll Use

  • Span 6 m, unbraced length 0.5 m
  • Section 400 × 140 × 16 × 10 mm
  • Superimposed dead 2 kN/m, live 5 kN/m
  • Material CSA G40.21 350W, Fy = 350 MPa
  • Deflection limit L/360 (floor)

Working Through It

Section classification (Cl 11.2, Table 2) checks flange and web ratios against Class 1/2/3 limits — both flange (4.38 against a Class 1 limit of 7.75) and web (36.8 against 58.80) come out Class 1, the most favourable classification.

The elastic critical moment Mu, computed from the classical warping-torsion formula using Iy, J, Cw and the unbraced length, comes out enormous at this short 0.5 m unbraced length — about 11,240 kN·m, far above the 0.67Mp ≈ 281 kN·m threshold. That puts the beam on the inelastic-interpolation branch, but the formula's own min() term caps the result at specifically the laterally-supported capacity: Mr = 377.6 kN·m either way.

Shear and deflection both check cleanly: φVr = 831.6 kN against a demand of just 32.36 kN, and mid-span deflection of 3.11 mm against a 16.67 mm limit.

What Governs, and Why

Deflection governs at utilisation 0.187, ahead of bending (0.129) and shear (0.039) — the same pattern seen across every code in this series for a beam braced well within its elastic-LTB range. LTB costs this beam nothing in practice, even though the calculation technically travels the inelastic branch rather than a separate laterally-supported check.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze Steel Beam module, free to try online — change any input and every downstream number recalculates instantly, with the governing code clause shown next to each result.

The free trial covers a curated set of flagship modules including this one. For the full catalogue — RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

How is CSA S16's LTB curve structurally different from AISC 360's?

AISC locates LTB behaviour on an unbraced-length axis, comparing Lb against two threshold lengths Lp and Lr. CSA S16 instead compares two moments directly — the elastic critical moment against 0.67Mp. Through one continuous inelastic-interpolation formula rather than a three-zone plastic/inelastic/elastic construction.

Why does the calculation still show the inelastic branch even though LTB doesn't reduce capacity?

Because Mu exceeding 0.67Mp technically routes the calculation through the inelastic formula rather than the simpler laterally-supported check — but that formula's own upper cap at φMp means the numeric result is identical either way once Mu is large enough.

Final Thoughts

CSA S16's single continuous LTB curve is a truly different mathematical structure from AISC 360's branched approach, even when the two produce the same practical answer for a well-braced beam.