A cold-formed steel tube joist's thin flange — often a width-to-thickness ratio near 50. Buckles elastically before it ever reaches yield stress at all, which is the normal, expected outcome for a CFS member, not an edge case, and it's exactly what the Direct Strength Method exists to capture.

Every check above runs automatically inside the Structyze CFS Beam / Joist module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

The Example We'll Use

  • Section 100 × 150 × 2.0 mm (box/tube)
  • Span 3.0 m
  • Factored moment 4.0 kN·m, shear 5.0 kN
  • Service UDL 3.5 kN/m
  • Material ASTM A1003 Grade 50, Fy = 345 MPa

Working Through It

Gross section properties give Sg ≈ 43,039 mm³ and a flat flange width w = 96 mm. The elastic local buckling stress, Fcrl = kπ²E/[12(1−ν²)](t/w)² with k = 4.0 for this closed box section, works out to 313.9 MPa.

The yield moment My = FySg ≈ 14.85 kN·m, but the elastic local buckling moment Mcrl = 13.51 kN·m is actually lower — meaning the thin flange genuinely does buckle before reaching yield. With λl = √(My/Mcrl) = 1.048, past the DSM transition of 0.776, the reduced capacity Mnl ≈ 12.24 kN·m, and φMn = 0.90(12.24) ≈ 11.01 kN·m.

Shear, checked on the two webs alone (Aw = 584 mm²), carries wide margin at utilisation 0.049 — nowhere close to governing.

What Governs, and Why

Deflection governs at utilisation 0.457, ahead of flexure (0.363) and far ahead of shear (0.049) — the normal pattern for a light-gauge member, where serviceability, not local-buckling-reduced strength, usually sets the practical limit before the DSM-reduced capacity ever becomes the binding constraint.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze CFS Beam / Joist module — this particular module is part of the full desktop catalogue rather than the free browser trial, since the trial only carries a curated flagship set. You can still try the free trial modules right now to see the same calculation style in action on RCC Beam, Column, Slab and a handful of others.

For CFS Beam / Joist and the rest of the full catalogue — 80+ components across RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why doesn't a thin CFS flange just yield the way a hot-rolled flange does?

A hot-rolled beam's compact flange is proportioned (by the rolling process and code classification limits) to reach full yield before any local instability sets in; a cold-formed tube's much thinner flange, often near a width-to-thickness ratio of 50, is thin enough that it buckles elastically first — DSM's job is to quantify exactly how much capacity that costs relative to the plain yield moment.

What buckling mode isn't checked here?

This is modelled as a closed 4-wall box/tube section, so global (lateral-torsional) buckling of the compression flange isn't checked — that mode matters far more for an open lipped-C-channel, which also needs a separate distortional-buckling check this closed-section example doesn't require.

Final Thoughts

The DSM flexural method is the clearest illustration in cold-formed steel design of why 'yield moment' and 'actual capacity' are two very different numbers for a thin-walled section.