A two-way restrained slab looks simple until you actually need the moment coefficients — IS 456 doesn't give a closed-form plate solution, it gives Annex D tables indexed by aspect ratio and edge-continuity condition, and picking the wrong row quietly wrong-foots every step after it.

Every check above runs automatically inside the Structyze RCC Slab module, free to try online — change any input and every downstream number recalculates instantly, with the governing code clause shown next to each result.

The Example We'll Use

  • Panel (clear) size 4 × 5 m, all four edges continuous
  • Thickness 150 mm, cover 20 mm (mild exposure)
  • Superimposed dead 1.5 kN/m², live 3 kN/m²
  • Concrete M20, steel Fe415
  • Reinforcement: 10 mm bars at 150 mm both directions (bottom), top steel at supports

Working Through It

Aspect ratio r = ly/lx = 5/4 = 1.25, under 2, so this is a truly two-way panel, not a one-way strip in disguise. Effective depth d = 150 − 20 − 5 = 125 mm, and the factored load wu = 1.5(25×0.15 + 1.5 + 3) ≈ 12.4 kN/m².

For Case 4 (all edges continuous) at r = 1.25, Table 26 gives αx− = 0.055 at the short-span support — the governing coefficient here. That gives Mx− = 0.055(12.4)(4)² ≈ 10.9 kN·m/m, worked through the Annex G-1.1 quadratic into Ast ≈ 258 mm²/m.

The Cl 26.5.2.1 minimum (180 mm²/m for HYSD) is below what bending needs, so the 10 mm bars at 150 mm (524 mm²/m) are governed by strength, not the code floor — and that same steel percentage (0.42%) feeds directly into the deflection modification factor.

What Governs, and Why

Deflection governs this slab at utilisation 0.82 — the allowable span/depth ratio works out to 26 × 1.5 ≈ 39 against an actual 4000/125 = 32, comfortably inside but the tightest check by far. Bending (0.48) and bar spacing (0.50) both carry real margin; this is the normal pattern for a slab sized more by serviceability than by strength.

Where Structyze Takes Over

Every check above runs automatically inside the Structyze RCC Slab module, free to try online — change any input and every downstream number recalculates instantly, with the governing code clause shown next to each result.

The free trial covers a curated set of flagship modules including this one. For the full catalogue — RCC, Steel, Composite, Timber, Masonry and more, across 20+ design codes — buy the full Structyze desktop app or see everything it does on the Software page.

Quick FAQ

Why does deflection usually govern a slab rather than bending?

A slab is thin and lightly stressed relative to its span, so the strength checks pass with room to spare long before the span/depth ratio does — unlike a beam, where shear or bending more often sets the section.

What changes for a one-way slab?

A one-way slab (supported on two opposite edges, or r ≥ 2) skips the Annex D coefficients entirely and is designed as an ordinary 1 m-wide beam strip — simpler, but the same minimum-steel and deflection checks still apply.

Final Thoughts

Reading the right row off an IS 456 moment-coefficient table by hand is easy to get subtly wrong once support conditions differ panel to panel across a floor plate.

Leave a Reply

Your email address will not be published. Required fields are marked *